FRENIC Multi
(*1)
FRENIC Multi
(*1) | Fuji's 4-pole standard motor |
(*2) | Rated capacity is calculated by assuming the output rated voltage as 220V for three-phase 200V series and 440V for three-phase 400V series. |
(*3) | Output voltage cannot exceed the power supply voltage. |
(*4) | When setting the carrier frequency (F26) to 3 kHz or less. Use the current ( ) or below when the carrier frequency setting is higher than 4kHz and continuously operating at 100%. |
(*5) | Obtained when a DC REACTOR is used. |
(*6) | Average braking torque obtained when reducing the speed from 60Hz with AVR control OFF (Varies with the efficiency of the motor.) |
(*7) | Average braking torque obtained by use of external braking resistor (standard type available as option) |
(*8) | Voltage unbalance [%] = Max voltage [V] - Min voltage [V] / Three-phase average voltage [V] x 67 (IEC 61800-3) If this value is 2 to 3%, use AC REACTOR (ACR: option). |
(*9) | The value is calculated on assumption that the inverter is connected with a power supply capacity of 500kVA (or 10 times the inverter capacity if the inverter capacity exceeds 50kVA) and %X is 5%. |